Power Management System (PMS)

Høglund Power Management System performs all necessary functions required to handle the power generation and main distribution onboard all types of vessels and configurations.

Seismic Vessel with Diesel Electrical Propulsion

HMA Solution: PMS for 2 switchboards, with modeselection and load control

Seismic Vessel with Diesel Electrical Propulsion

HMA Solution: Switchboard breaker control with blackout reconfiguration

Jackup - Windmill Installation vessel

HMA Solution: PMS for 4 switchboards, with modeselection and load control

Jackup - Windmill Installation vessel

HMA Solution: Switchboard breaker control with blackout reconfiguration

Jackup - Windmill Installation vessel

HMA Solution: Heavy Consumer Control

LNG Carrier with Dual Fuel engines (HFO/MDO and LNG)

HMA Solution: PMS with Fork generator and BOG Control

LNG Carrier with Dual Fuel engines

HMA Solution: Switchboard breaker control with blackout reconfiguration

Seismic Vessel with mechanical propulsion

HMA Solution: PMS with Aux Gens, Shaft Gens and Clutch Control

Seismic Vessel with mechanical propulsion

HMA Solution: PMS with Aux Gens, Shaft Gens and Clutch Control

Other functionalities included are:

Other functionalities included are:

Load dependent start/stop

handles the start/stop of the engine in situations when this is required by the power demand.

Pre-warning

a function which automatically starts the next available generator if any engine conditions which will lead to a shutdown of the engine is getting critically near the shutdown limit

Shut down function

when an engine shutdown is detected, the PMS will immediately disconnect affected generator and start the next one in the pre-defined sequence.

Load reduction

each thruster drive receives an available power signal from the PMS, which prevents the generators from overloading, reducing the risk for a total blackout in case a generator trips.

Heavy Consumers

Controlling start of heavy consumers by looking at connected and available power on the switchboard. Starting new engine / connecting new generator if needed. (engine/generator)

Blackout Reconnection

handles both partial and total blackouts, reconnecting important breakers after blackout

Switchboard configuration

configuration of tie breakers/swb breakers depending on operational mode.